Still deciding? Get samples of $ !
Request Sample
|
| Customization: | Available |
|---|---|
| After-sales Service: | Support Online Checking |
| Warranty: | One Year Warranty |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Voltage | Nominal Voltage (Un): 3x220/380V ~ 3x230/400V Voltage Range: 0.7Un to 1.3Un of Nominal Voltage | |
Current | Basic Current: lb = 5/10A | Max Current: lmax =60/80/100A |
Starting Current: 0.4%lb | Max Current for Accurate Metering: 1.2lmax | |
Frequency | 50Hz ± 5% | |
Connection Type | 3P4W BS Mounting Foot, Symmetrical L1inL2inL3inNinNoutL3outL2outL1out 3P4W BS Mounting Foot, Asymmetrical L1inL1outL2inL2outL3inL3outNinNout | |
Power Consumption | Voltage Circuit: <2V, 10VA | Current Circuit: <1VA |
Accuracy | Active: Class 1.0 | Reactive: Class 2.0 |
Real-time Clock | Accuracy within 0.5s per day at 23℃ | |
Standard | Compliance with lEC 62052-11, IEC 62053-21, IEC 62053-23; SANS 1524-1, IEC 2054-21, IEC 62056-42, IEC62056-46, IEC 62056-53, IEC 62052-31, IEC 62055-31 | |
Measured Values | Active: kWh Reactive: kvarh | |
Instantaneous values: kW, kvar, kVA, lrms, Vrms, Frequency, Power factor | ||
Meter LCD Display | 9 characters of 7 segment display | Digital size 5.9mmx11.3mm |
LCD display available without main power | With backlight | |
Internal Battery | Lithium | Lifetime: ≥10 years |
Supercapacitor integrated in case of internal battery failure | ||
External Battery | Easily replaceable(external) | |
Voltage: 3.6V | Lifetime: 15 years | |
Environmental Conditions | Operation temperature: -40°C to +70℃ | |
Storage temperature: -40°C to +85°C | ||
Relative humidity: 5%~95% with 95%RH at 45℃ non-condensing | ||
Remote Communication Interface | Uplink: Two way communication between HES by 4G plug-in module(Fall Back to 3G,2G)/G3-PLC/Hybrid G3-PLC+RF/BPLC | |
Communication Port | Optical Port lEC 62056-21 standard, sealable | |
GNSS(Optional) | GPS, BEIDOU, GLONASS | |
Protocol | DLMS/COSEM | |
IP Degree | IP54(IEC 60529) | |
Insulation Degree | Insulation Degree: ll | |
Weight | Around 1.7Kg | |
Material | PC+GF, self-extinguishing of resistance to heat, fire and flame spread, UV stable | |
Auxiliary Ports | RS485 Output | |
Insulation Test | AC voltage 4KV, 50Hz 1min | |
Impulse Withstand Voltage | 6kV 1.2/50us | |
Electromagnetic Compatibility(EMC) | Electrostatic discharges: Contact 8kV, air 15kV | |
Electrical fast transient: 4kV | ||
Immunity to electromagnetic RF fields: 10V/m with current, 30V/m without current | ||
Surge lmmunity: 4kV | ||
440V for 48 hours | ||
Payment Mode | Standard Transfer Specification(STS) compliance, prepayment and post-payment mode configurable | |